PCC & MDC

ABB Distribution Boards (DBs) – ranges up to 6000A

ArTu L Range

Technical characteristics

  Wall-mounted D=204mm Floor-standing D=240mm
Compliance with Standards CEI EN 60439-1/IEC 61439-1-2 CEI EN 60439-1/IEC 61439-1-2
Rated service voltage Ue up to 690 V up to 690 V
Rated insulation voltage Ui up to 1000 V up to 1000 V
Rated frequency 50-60 Hz 50-60 Hz
Rated impulse withstand voltage Uimp 6 kV 8 kV
Rated current In up to 400 A up to 800 A
Rated short-time short-circuit withstand current Icw up to 25 kA up to 35 kA
peak current Ipk up to 52.5 kA up to 74 kA
Degree of protection IP 31 without door 31 without door
43 with door 43 with door

Go to top of the page

ArTu M (monobloc) Range

Technical characteristics

  Wall-mounted D=115/165mm Floor-standing D=195mm
Compliance with Standards CEI EN 60439-1/IEC 61439-1-2 CEI EN 60439-1/IEC 61439-1-2
Rated service voltage Ue up to 690 V up to 690 V
Rated insulation voltage Ui up to 1000 V up to 1000 V
Rated frequency 50-60 Hz 50-60 Hz
Rated impulse withstand voltage Uimp 25 kV 35 kV
Rated current In up to 250 A up to 630 A
Rated short-time short-circuit withstand current Icw up to 25 kA up to 35 kA
Rated peak short-circuit current Ipk up to 52.5 kA up to 74 kA
Degree of protection IP 65 with door 31 without door
65 with door

Go to top of the page

ArTu K Range

Technical characteristics

  • Compliance with Standards CEI EN 60439-1/IEC 61439-1-2
  • Test of vibration for structure ArTu K
  • Test of antiseismic
  • according to IEC 60068-2-57 Standard
  • according to IEE Std 693 Standard
  • Rated service voltage Ue up to 1000 V
  • Rated insulation voltage Ui up to 1000 V
  • Rated frequency 50-60 Hz
  • Rated impulse withstand voltage Uimp 8 kV
  • Rated current In up to 6300 A
  • Rated short-time short-circuit withstand current Icw up to 105 kA
  • Rated peak short-circuit current Ipk up to 254 kA
  • Degree of protection IP
  • 31 without door
  • 41 without door with accessories
  • 65 with door up to 4000A
  • 41 with door up to 6300A

Go to top of the page

ABB Sub Main Distribution Boards (SMDBs)

ABB Sub Main Distribution Boards (SMDBs) – ranges up to 800A

Multi Purpose PowerpackRange

Characteristics and Specifications

Application

A range of empty multi purpose enclosures and enclosures with components mounted: load break switches, changeover switches, and switch fuses.

Technical Data

  • Standard: IEC 947, BS EN 947 parts 1 & 3
  • Max. load: 800 amps
  • Max. voltage: 240 / 415 V ac, 50 / 60 Hz
  • Range: 8 sizes
  • Degree of protection: IP 54
  • Enclosure material: Cold rolled sheet steel 1 mm sizes 1 to 6, 1.5 mm sizes 7 & 8 (Aluzinc steel on request)
  • Enclosure finish: Grey, RAL 7035

Go to top of the page

Unikit Range

Characteristics and Specifications

Technical Details:

  • Standard (Regulations): IEC 439-1/EN 60439-1/BS EN 60439-1&3
  • Max. load
  • Wall mounted (UNIKIT 150): 250 A
  • Free standing (UNIKIT 250): 630 A
  • Max. voltage: 400V ac, 50/60 Hz
  • Rated insulation voltage Ui: 1000 V AC
  • Rated operational voltage Ue: 690 V AC
  • Degree of protection:
  • IP 30 without Door
  • IP 41 with Door
  • IP 54 on request
  • Colour: RAL 7035 (1013 available on request)
  • Rated short time withstand current: 35 KA
  • Enclosure material: Cold rolled sheet steel 1.5 mm
  • (Aluzinc steel on request)

Go to top of the page

Mirage Range

250 A Technical details

  • Standard: IEC 439-1, EN 60439-1/BS EN 60439-1 &3
  • Max. load: 250 Amp
  • Max. voltage: 415V ac, 50/60 Hz
  • Rated insulation voltage: 1000V ac
  • Rated operational voltage: 690 V ac
  • Range: 2, 4, 6, 8, 12 and 16 TP&N ways
  • Incoming Device: Max. 250 Amp, TP MCCB size T3
  • Outgoing Device: Max. 125 Amp, TP or SP MCB S800
  • Protection degree: IP 42 (IP54 as an option on request)
  • IP 20 for pan assembly
  • Color: RAL 7035
  • Rated short time withstand current: 35 KA at 415V. 0.25 pf
  • Rated peak withstand current: 73.5 KA at 415V. 0.25 pf
  • Rated impulse withstand voltage: 2.5 kV
  • Enclosure material: Cold rolled sheet steel 1.5 mm
  • (ALUZINK steel on request)

400 A Technical details

  • Standard: IEC 439-1, EN 60439-1/BS EN 60439-1 &3
  • Max. load: 400 Amp
  • Max. voltage: 415V ac, 50/60 Hz
  • Rated insulation voltage: 1000V ac
  • Rated operational voltage: 690 V ac
  • Range: 4, 6, 8, 12 and 16 TP&N ways
  • Incoming Device: Max. 400 Amp, TP MCCB size T5
  • Outgoing Device: Max. 125 Amp, TP or SP MCB S800
  • Protection degree: IP 42 (IP54 as an option on request)
  • IP 20 for pan assembly
  • Color: RAL 7035
  • Rated short time withstand current: 36 KA at 415V. 0.25 pf
  • Rated peak withstand current: 75.6 KA at 415V. 0.25 pf
  • Rated impulse withstand voltage: 6 kV
  • Enclosure material: Cold rolled sheet steel 1.5 mm
  • (ALUZINK steel on request)

630 A Technical details

  • Standard: IEC 439-1, EN 60439-1/BS EN 60439-1 &3
  • Max. load: 630 Amp
  • Max. voltage: 415V ac, 50/60 Hz
  • Rated insulation voltage: 1000V ac
  • Rated operational voltage: 690 V ac
  • Range: 4, 6, 8, 12 and 16 TP&N ways
  • Incoming Device: Max. 630 Amp, TP MCCB size T5-630 PR221DS
  • Outgoing Device: Max. 125 Amp, TP or SP MCB S800
  • Protection degree: IP 42 (IP54 as an option on request)
  • IP 20 for pan assembly
  • Color: RAL 7035
  • Rated short time withstand current: 50 KA at 415V. 0.25 pf
  • Rated peak withstand current: 105 KA at 415V. 0.25 pf
  • Rated impulse withstand voltage: 6 kV
  • Enclosure material: Cold rolled sheet steel 1.5 mm
  • (ALUZINK steel on request)

Go to top of the page

Distribution Boards

ABB Distribution Boards (DBs) – ranges up to 250A

Protecta compact Range

Characteristics and Specifications

·          Standard: IEC 439- 3 & BS 60439 part 1 & 3

Single row type

  • Range: 6, 9, 13, 18 and 22 Modules

Multi row type

  • Max. load: 100 amps
  • Max. voltage: 230 / 400 V ac, 50 / 60 Hz
  • Range: 16, 32, 48, 64 and 80 modules
  • 1, 2, 3, 4 and 5 rows

Busbar type

  • Max. load: 250 amps
  • Max. voltage: 230 / 400 V ac, 50 / 60 Hz
  • Range: 4, 6, 8, 12, 16, 20 and 24 TP&N ways
  • 12, 18, 24, 36, 48, 60 and 72 SP&N ways
  • Degree of protection: IP 41, pan assemblies IP 20
  • Enclosure material: Cold rolled sheet steel
  • Box and cover 1 mm
  • (Aluzinc steel on request)
  • Enclosure finish: Gray, RAL 7035
  • Fault level: 35 kA

Go to top of the page

Mini Center Range

Characteristics and Specifications

Technical Data

·          Standard: IEC 439- 3 & BS 60439 part 1 & 3

Multi row type

  • Max. load: 100 amps
  • Max. voltage: 230 / 400 V ac, 50 / 60 Hz
  • Range: 20, 32, 48, 64 and 80 modules
  • 1, 2, 3, 4 and 5 rows

Busbar type

  • Max. load: 160 amps
  • Available in 250 amps on request
  • Max. voltage: 230 / 400 V ac, 50 / 60 Hz
  • Range: 4, 6, 8, 12 and 16 TP&N ways
  • 12, 18, 24, 36 and 48 SP&N ways
  • Degree of protection: IP 41, pan assemblies IP 20
  • Enclosure material: Cold rolled sheet steel
  • Box and cover 1 mm
  • (Aluzinc steel on request)
  • Enclosure finish: Gray, RAL 7035
  • Fault level: 35 kA

Go to top of the page

ECO Range

Characteristics and Specifications

  • Standard: IEC 439- 3 & BS 60439 part 1 & 3
  • Degree of protection: IP 41
  • Enclosure material: Cold rolled sheet steel
  • Box and cover 1 mm
  • Enclosure finish: Grey, RAL 7035
  • Flush or surface mounting.

Multi row type

  • Max. load: 100 A
  • Max. voltage: 230 / 400 V AC, 50 / 60 Hz
  • Range: 28, 42 and 56 modules 2, 3 and 4 rows

Busbar type

  • Max. load: 160 A
  • Max. voltage: 230 / 400 V AC, 50 / 60 Hz
  • Range: 4, 6, 8 and 12 TP&N ways 12, 18, 24 and 36 SP&N ways
  • Fault level: 35 kA

Go to top of the page

Consumer Units

ABB Consumer Units (CUs) – ranges up to 125A

MISTRAL65 Range

Characteristics and Specifications

  • IP65 rated
  • Resistant to a wide range of chemical agents
  • Suitable for Industrial, Commercial and Residential sectors
  • 100% Halogen-free thermoplastic which is completely recyclable
  • Transparent or Opaque doors
  • Between 4 and 72 modules
  • Refined and sleek design
  • Cable optimization
  • DIN rail positions for both MCBs and MCCBs
  • Maximum currents up to 125A
  • Mechanical impact resistance IK09
  • Reference standard IEC60670 – EN60439-3

Go to top of the page

Comby Range

Characteristics and Specifications

  • IP30 rated
  • Suitable for Industrial, Commercial and Residential sectors
  • Transparent or Opaque flaps
  • Between 7, 10, 16 and 20 modules
  • Maximum currents up to 100A
  • Reference standard IEC 439-1&3, BS 60439-1&3

Go to top of the page

Housemaster Compact Range

Characteristics and Specifications

  • IP30 rated
  • Suitable for Industrial, Commercial and Residential sectors
  • Transparent or Opaque flaps
  • Between 4, 7, 11, 16 and 20 SP & N ways, Split load 8, 12, 16 ways
  • Maximum currents up to 100A
  • Material in sheet steel range or molded plastic
  • Reference standard IEC 439-1&3, BS 60439-1&3

Go to top of the page